Top Qs
Timeline
Chat
Perspective

SAIDI

Reliability index used by electric power utilities From Wikipedia, the free encyclopedia

Remove ads
Remove ads

The system average interruption duration index (SAIDI)[1] is commonly used as a reliability index by electric power utilities. SAIDI is the average cumulative outage duration for each customer served, and is calculated as:

where is the number of customers and is the annual outage time for location , and is the total number of customers served. In other words,

SAIDI is measured in units of time, often minutes or hours; it is usually measured over the course of a year. According to IEEE Standard 1366–1998, the median value for North American utilities is approximately 1.50 hours. According to the U.S. Energy Information Administration annual electric power industry report, it is 2.0 hours, rising to the range of 3.5 to 8 hours, when "major events" are included.[2]

Remove ads

Comparison of SAIDI by country

The following is a table of SAIDI for different countries, calculated using the methodology in the World Bank's Doing Business 2016-2020 studies:

More information Country, Population (million) in 2020 ...
Remove ads

References

Loading content...
Loading related searches...

Wikiwand - on

Seamless Wikipedia browsing. On steroids.

Remove ads