Branch of electrical power engineering From Wikipedia, the free encyclopedia

Power system protection
Remove ads

Power system protection is a set of techniques and power grid equipment used to limit the damage caused by an electrical fault and safeguard other components of the grid, like generators and transmission lines.[1] The term is also used for a branch of electrical power engineering that deals with the protection.[2] There is an overlap between the power system protection and power system operations, as the protection equipment, like other switchgear, can be used for operations.[3]

Thumb
Dead-tank circuit breaker

The protection devices are used to protect the power systems from faults by detecting the faults and taking action ("tripping"). P. M. Anderson distinguishes the reactionary devices, like protective relays, that "clear" a fault by isolating it from the rest of system and safeguard devices that address the source of the hazard (for example, an emergency core cooling system of a nuclear reactor). As a discipline, power system protection mostly deals with the reactionary devices.[4]

Remove ads

Protection devices

Summarize
Perspective

Power system protection relies on few basic elements:[5]

  • a sensor performs a measurement (test) of a value (for example, of electric current in a transmission line);
  • a comparator checks the test result against a threshold that the result is not supposed to cross during normal operation (for example, the maximum acceptable current value when testing for the overcurrent condition). Ability to identify an abnormal condition is called sensitivity;[6]
  • a timing element (delay) that checks for the persistence of the condition (for example, if a fault had been cleared by another protection device with a smaller delay setting, this device should not take any action);
  • action element (typically circuit-opening).

Protective devices include,[7] under a common label of "switchgear":[8]

Connecting the protective devices to the grid usually involves additional hardware:

With the exception of the breaker, the components of the protective device are frequently deployed in a redundant fashion.[13]

Remove ads

Protective zones

Summarize
Perspective
Thumb
Overlapping protection zones: single-line diagram depicts generators at the top connected to voltage transformers, (vertical) transmission lines and (horizontal) busbars. The switch symbols are protective relays. Zone boundaries are indicated by colored dashed lines

The objective of a protection scheme is to keep the power system stable by isolating only the components that are under fault, whilst leaving as much of the network as possible in operation, thus minimizing the loss of load.[14] This property of the protection system is called selectivity.[6] To achieve selectivity, the power system is subdivided into protective zones, each containing a power system component that should be protected. Each zone has its own protection device(s) and provides sensitivity to faults within its boundaries. The boundaries of zones overlap to leave no part of grid without protection. The overlapping regions of sensitivity have a drawback of multiple relays possibly tripping when the fault is in the overlapped area.[15] For example, unless special arrangements are made, a short circuit above the relay A, but still within the blue zone on the diagram, might cause overcurrent conditions in relays A, C, and D and cause them to trip, with the two latter trips being redundant. This can be avoided by using specialized relays (distance or directional ones) or by coordinating the relay actions using a communication channel ("pilot").

Backup

The power protection system needs to be resilient to its own malfunctions. Thus it includes backup protection devices. For example if the fault is in the top left red zone, but outside the blue zone, it is expected to be handled by the "primary" relay A. If the relay A malfunctions and cannot clear the fault, the backup relays C and D in the adjacent (blue) zone will trip. This can be arranged without coordination (for example, the delay setting of C and D can be higher so they do not act if A succeeds in clearing the fault)[16] or through coordination via a pilot.[citation needed] The term local backup is used when the backup relays are within the same zone as the "primary" one being duplicated.[17]

Local back-up protection, like the primary protective device, will isolate the elements of the plant affected by the fault to clear the latter. Adjacent-zone ("remote") back-up protection will generally isolate both the affected and unaffected items of plant to clear the fault.

Remove ads

Fault types

Summarize
Perspective

The faults can be classified by their level of permanence that affects the possibility of autoreclosing:[18]

  • a transient fault clears quickly once the line is opened (for example, a flashover over an insulator on the transmission tower caused by lightning). A quick reclosing with not cause the fault to reappear. The transient faults represent the vast majority of faults on the overhead transmission lines;
  • a semipermanent fault, like tree contact, are faults that might clear themselves if allowed to burn for a short time (a tree branch might burn away). Semipermanent faults occur more frequently in the subtransmission lines and electric distribution;
  • a permanent fault must be repaired. Almost all the faults on the underground power cable are permanent.

Many pieces of the grid equipment can develop internal problems. For these devices, the faults can be classified into internal and external. As an example of the internal fault, a transformer might develop overpressure inside it containment vessel with its root cause (for example, local overheating) not triggering any other alarms. For the same transformer, an overload condition would represent an external fault.[19]

Relay types

Summarize
Perspective
Thumb
A digital ("numerical") multifunction protective relay for distribution networks. A single such device can replace many single-function electromechanical relays, and provides self-testing and communication functions.

The relays can be classified by their sensitivity to the location of a fault:

  • a nondirectional relay does not provide an information on which side of it the fault is located, this is the simplest form of the overcurrent relay. For example, in a radial system of electrical power distribution, the current always flow to the load spokes, so there is not need to sense its direction, as an overcurrent condition always indicates a short circuit on the load side;[20]
  • a directional relay compares the current phase with the reference and performs action only if the direction to the fault matches the selected one;[21]
  • a differential relay compares the values of electrical measurements on the input and output of a protected device. For example, in an electrical transformer, input and output voltage and current values are related through the transformer ratio, and large deviations from this constant indicate a fault;[22]
  • a distance relay determines the distance of the fault by calculating the line electrical impedance as seen by the relay based on observe current, voltage, and the phase difference between them. The knowledge of distance can be used to prevent tripping when the fault is in the wrong zone;[21]
  • a pilot protection relay senses the conditions on the other end of the line through a communication channel (wire pilot, carrier pilot, microwave pilot, and fiber-optic pilot).[23]

In the 21st century a lot of testing for abnormal conditions is performed by multifunctional numerical relays that use computers for calculations. Individual measurements use cryptic identifiers from the ANSI device numbers list, like "50" for the "Instantaneous Overcurrent Relay" or "87L" for the "Segregated Line Current Differential".

Historically, the power industry went through multiple generations of sensors and comparators, retaining the terminology and some of the devices:

  • electromechanical relays are the simplest devices used for protection since the early days of electrical power industry. For example, an induction disk overcurrent relay is an overcurrent relay that uses an induction disk as a sensor and timing element;[24]
  • electronic relays, with comparators and level detectors were introduced slowly over a long period of time starting in the 1930s. The process accelerated with the arrival of transistor in 1950s.[25]
  • digital relays were proposed in 1969, but became widespread only with the introduction of microprocessor in the early 1970s.[25]
Remove ads

Types of protection

Summarize
Perspective

Transmission protection

High-voltage transmission lines typically form a mesh-like grid, so the current might be flowing into the fault from either direction, making the non-directional relays mostly unsuitable for protection, so the distance, and pilot relays are typically used.[26] The use of directionla relays is not always possible.[27]

Ground fault

In a grounded neutral transmission line, the phase relays might detect and clear a ground fault. However, since almost all faults on high-voltage lines are of the one-phase-to-ground variety, specialized ground relays are used for quick reaction.[28] These relay utilize the zero-sequence current for detection. During the normal operation, the zero-sequence current is very small, so a high current value that depends on the network configuration, not on the (varying) load, is a convenient and reliable indicator of a ground fault.[29]

Generators

Generators are expensive and complex pieces of the grid equipment, thus the larger machines use tens of types of protection. Practically every generator has the stator protection, usually using differential relays.[30] The internal failures of generators are unusual, so the protective relays trips are very rare.

Transformers

Not only the transformers are expensive, but it might take a long time to replace a failed large transformer.[31] Electrical protection of a transformer mostly uses the differential relays.[32] This protection can be combined with the one of the busbar[33] or generator.[34]

Low-voltage networks

The low-voltage network generally relies upon fuses or low-voltage circuit breakers to remove both overload and earth faults.

Remove ads

Coordination

Summarize
Perspective

Protective device coordination is the process of determining the "best fit" timing of current interruption when abnormal electrical conditions occur. The goal is to minimize an outage to the greatest extent possible. Historically, protective device coordination was done on translucent log–log paper. Modern methods normally include detailed computer based analysis and reporting.

Protection coordination is also handled through dividing the power system into protective zones. If a fault were to occur in a given zone, necessary actions will be executed to isolate that zone from the entire system. Zone definitions account for generators, buses, transformers, transmission and distribution lines, and motors. Additionally, zones possess the following features: zones overlap, overlap regions denote circuit breakers, and all circuit breakers in a given zone with a fault will open in order to isolate the fault. Overlapped regions are created by two sets of instrument transformers and relays for each circuit breaker. They are designed for redundancy to eliminate unprotected areas; however, overlapped regions are devised to remain as small as possible such that when a fault occurs in an overlap region and the two zones which encompass the fault are isolated, the sector of the power system which is lost from service is still small despite two zones being isolated.[35]

Remove ads

Disturbance-monitoring equipment

Disturbance-monitoring equipment (DME) monitors and records system data pertaining to a fault. DME accomplish three main purposes:

  • model validation,
  • disturbance investigation, and
  • assessment of system protection performance.[36]

DME devices include:[37]

  • Sequence of event recorders, which record equipment response to the event
  • Fault recorders, which record actual waveform data of the system primary voltages and currents
  • Dynamic disturbance recorders (DDRs), which record incidents that portray power system behavior during dynamic events such as low frequency (0.1 Hz – 3 Hz) oscillations and abnormal frequency or voltage excursions
Remove ads

Performance measures

Summarize
Perspective

Protection engineers define dependability as the tendency of the protection system to operate correctly for in-zone faults. They define security as the tendency not to operate for out-of-zone faults. Both dependability and security are reliability issues. Fault tree analysis is one tool with which a protection engineer can compare the relative reliability of proposed protection schemes. Quantifying protection reliability is important for making the best decisions on improving a protection system, managing dependability versus security tradeoffs, and getting the best results for the least money. A quantitative understanding is essential in the competitive utility industry.[38][39]

  • Reliability: Devices must function consistently when fault conditions occur, regardless of possibly being idle for months or years. Without this reliability, systems may cause costly damages.
  • Selectivity: Devices must avoid unwarranted, false trips.
  • Speed: Devices must function quickly to reduce equipment damage and fault duration, with only very precise intentional time delays.
  • Sensitivity: Devices must detect even the smallest value of faults and respond.
  • Economy: Devices must provide maximum protection at minimum cost.
  • Simplicity: Devices must minimize protection circuitry and equipment.

Reliability: Dependability vs Security

There are two aspects of reliable operation of protection systems: dependability and security.[40] Dependability is the ability of the protection system to operate when called upon to remove a faulted element from the power system. Security is the ability of the protection system to restrain itself from operating during an external fault. Choosing the appropriate balance between security and dependability in designing the protection system requires engineering judgement and varies on a case-by-case basis.